We've confirmed there is a problem, we're working to resolve it. The PDU power distribution wasn't balanced, each PDU is 32A with 2 breaks, each break has 16A, break #2 on left PDU has borderline usage of 12A while the break #1 only 3A, probably a peak occurred and reached 16A. We rebalanced the power usage between the breaks. Checked right side PDU breaks and usage. Furthermore high consumption 2 servers have been identified, customer notified about schedule of migration to other rack next week. Currently everything is stable.
Half hour ago a power outage occurred at rack F2 (bottom side) in the Shacham data center. Power has since been fully restored. Our team is actively investigating the root cause to prevent recurrence.
We will provide further updates as necessary.